We offer Acoustic Treatment for DG Rooms. The Noise is control by providing Acoustic lining on walls & ceiling, all ordinary doors / shutters are to be convert in to sound proof doors. The proper Air ventilation system is designed to allow the maximum aspiration and cooling airflow required so the engine does not overheat. Axial flow fan of required size & numbers provided for proper Air ventilation. Acoustic louvers, splitter & Insulated ducts are provided to suppress the noise where required.
Standards/Guidelines for control of Noise Pollution as per Govt. of India in respect to D.G. Sets
Mandatory acoustic enclosure/acoustic treatment of room for stationary DG sets (5 KVA and above)
Noise from the DG set should be controlled by providing an acoustic enclosure or by treating the room acoustically.
The acoustic enclosure/acoustic treatment of the room should be designed for minimum 25 dB(A) Insertion Loss or for meeting the ambient noise standards, which ever is on the higher side (if the actual ambient noise is on the higher side, it may not be possible to check the performance of the acoustic enclosure/acoustic treatment. Under such circumstances the performance may be checked for noise reduction upto actual ambient noise level, preferably, in the night time). The measurement for Insertion Loss may be done at different points at 0.5m from the acoustic enclosure/room, and then averaged.
The DG set should also be provide with proper exhaust muffler with Insertion Loss of minimum 25 dB(A).
|